Search
Select Page

UQDB couplings

  • Blind-Mate version of the OCP UQD quick disconnect standard
  • Two sizes: UQDB02 and UQDB04
  • Leak-free quick disconnect for data center liquid cooling

 

CEJN OCP UQDB (Universal Quick Disconnect Blind-Mate) is a Blind-Mate version of the UQD quick disconnect designed for data center liquid cooling. UQD is a global quick disconnect standard developed by the Open Compute Project (OCP).

UQDB couplings enable leak-free Blind-Mate connections in liquid cooling systems. The series is available in two sizes: UQDB02 with a 3.2 mm nominal flow diameter and UQDB04 with a 6.4 mm nominal flow diameter. Both sizes have a max working pressure of 10 bar.

 

Applications: Data center liquid cooling systems.

For more information about our products, call us at 010 778 1400 or email us at info@pneumacon.fi.

Technical data

Nominal flow diameterUQDB02: 3.2 mm / UQDB04: 6.4 mm
Max working pressure10 bar
Min burst pressure40 bar (580.15 PSI)
Temperature range−20 °C – +65 °C
Main materialStainless steel (AISI 303)
Seal materialEPDM
Kv (double shut-off)UQDB02: 0.29 / UQDB04: 0.75
Cv (double shut-off)UQDB02: 0.34 / UQDB04: 0.87

More tools are featured in tool catalog.

Technical data:

Coupling (Sockets)Part No.Nominal flow diameterSeal materialLengthDiameter
UQDB0210 153 19223.2 mmEPDM33.6 mm16.8 mm
UQDB0410 153 19246.4 mmEPDM42.8 mm21.8 mm
Nipple (Plug)Part No.Nominal flow diameterSeal materialLengthDiameter
UQDB0210 153 69223.2 mmEPDM36.1 mm21 mm
UQDB0410 153 69246.4 mmEPDM45.4 mm24.6 mm